Interpreting the JSON Data from IAMMETER`s Energy Meter
This article primarily introduces the definition of JSON data for electric meters.
Please note: this article is not intended for the general user; it's specifically for those who wish to integrate IAMMETER`s energy meter into 3rd party system. If you are just using the electric meter within the IAMMETER system, there is no need to focus on the details of the JSON content.
This includes scenarios such as uploading energy meter data to a third-party server or integrating the energy meter into an open-source platform locally. Regardless of whether the meter is set up to upload data to a third-party server (using HTTP/HTTPS, TCP/TLS, MQTT) or to retrieve data through a local API, the JSON format remains consistent across all methods.
JSON format
Three phase meter
Below are the various types of three-phase meters offered by IAMMETER:
Hardware | Phase | CT Rating | IAMMETER-cloud | NEM | Reactive | Remark |
---|---|---|---|---|---|---|
WEM3080T | 3 | 150,250,500 | Yes | Yes | Yes | |
WEM3046T | 3 | N/A | Yes | Yes | Yes | CT is not in package |
WEM3050T | 3 | 150 | 3 Months | Yes | Yes |
How to choose IAMMETER`s 3 phase meter
JSON format of 3 phase meter
{
"method":"2-5",
"mac":"B0F8933C1DF7", //mac
"version":"i.75.98.66",//FW version
"server":"em",
"SN":"12345678",//Serial Number
"EA":{
"Reactive":[
[
-953, //reactive power of phase A,unit:KVAR
56.789, //reactive energy(inductive) of phase A ,unit:KVARH
65.879 //reactive energy(capacitive) of phase A ,unit:KVARH
],
[
-948, //reactive power of phase B,unit:KVAR
78.659,//reactive energy(inductive) of phase B ,unit:KVARH
2.323 //reactive energy(capacitive) of phase B ,unit:KVARH
],
[
-944, //reactive power of phase C,unit:KVAR
65.245,//reactive energy(inductive) of phase c ,unit:KVARH
6.666 //reactive energy(capacitive) of phase C ,unit:KVARH
]
]
},
"Datas":[
[
219.7, //voltage of Phase A,unit:V
0.5, //current of phase A,unit :A
-54.9, //active power of phase A, unit :w
11.337, //forward active energy of phase A, unit :Kwh
11.201, //reverse active energy of phase A,unit Kwh
49.99, //Frequency of phase A
0.5 //power factor of phase A
],
[
219.9, //voltage of Phase B.unit:V
0.499, //current of phase B,unit :A
-55.4, //active power of phase B, unit :w
11.039, //forward active energy of phase B, unit :Kwh
10.908, //reverse active energy of phase B,unit Kwh
49.99, //Frequency of phase B
0.5 //power factor of phase B
],
[
219.9,//voltage of Phase C,unit:V
0.499, //current of phase C,unit :A
-55.7, //active power of phase C, unit :w
10.975, //forward active energy of phase C, unit :Kwh
10.846, //reverse active energy of phase C,unit Kwh
49.99, //Frequency of phase C
0.51 //power factor of phase C
]
]
}
Please note:
- The measurement of reactive power (KVAR) and reactive energy (KVARH) is only activated when you enable their tracking through this API.
- active power = Voltage * Current * power factor
single phase meter
WEM3080:smart single Phase Energy Meter Wi-Fi,Cloud/app,electric sub meters
JSON format for single phase meter
{
"method": "uploadsn",
"mac": "B0F8932A295C", //mac
"version": "i.75.98.71y",//FW version
"server": "em",
"SN": "12345678", //serial number
"Data": [
228.91, //voltage,unit:V
1.61, //current ,unit :amp
225, //active power, unit :w
15066.47, //forward active energy, unit:kwh
0 //reverse active energy, unit:kwh
]
}
Guidelines for Integrating IAMMETER Products into 3rd party system
All IAMMETER products are crafted for seamless integration with third-party servers using protocols like HTTP/HTTPS, MQTT, TCP/TLS, or with various open-source platforms such as Home Assistant, Node-RED, ioBroker, OpenHAB, Zabbix, and ThingsBoard. This straightforward integration capability is a hallmark feature of IAMMETER.
This article is applicable not just to the WEM3050T, but to all three-phase meters from IAMMETER. How to utilize the WEM3050T, excluding IAMMETER-cloud